1. Inleiding

This manual provides detailed instructions for the installation, operation, and maintenance of the Watts 009M2 Reduced Pressure Zone (RPZ) Backflow Preventer. This device is designed to protect potable water supplies from contamination due to backpressure or backsiphonage from non-potable sources. It is crucial to read and understand all instructions before installation and use to ensure proper function and safety.

The Watts 009M2 RPZ assembly features a compact, modular design for easy maintenance, with a single access cover for in-line repairs. It is suitable for continuous pressure piping applications and cross-connections identified as health hazards.

2. Belangrijke veiligheidsinformatie

3. Product voorbijview en componenten

The Watts 009M2 Reduced Pressure Zone Backflow Preventer is constructed with a durable bronze body and features NPT end connections. Key components include:

Watts 009M2 Reduced Pressure Zone Backflow Preventer
Figure 1: Watts 009M2 Reduced Pressure Zone Backflow Preventer. This image shows the bronze body, quarter-turn shutoff valves with green handles, and multiple test cocks on top.

4. Installatie en installatie

  1. Controle vóór installatie:
    • Verify that the product model (009M2) and size (2 inch) match your requirements.
    • Inspect the unit for any shipping damage.
    • Ensure all necessary tools and materials for installation are available.
  2. Voorbereiding van de locatie:
    • Choose an installation location that allows for easy access for testing and maintenance.
    • Ensure adequate drainage for the relief valve discharge.
    • The device should be installed horizontally, with the relief valve pointing downwards.
  3. Leidingverbinding:
    • Flush the upstream piping thoroughly to remove any debris before connecting the backflow preventer.
    • Connect the inlet and outlet piping to the NPT connections on the device. Use appropriate thread sealant.
    • Avoid overtightening connections to prevent damage to the bronze body.
    • Ensure the flow arrow on the device body matches the direction of water flow.
  4. Relief Valve Drain:
    • Connect a drain line to the relief valve outlet. The drain line must be adequately sized and sloped to allow for free discharge and prevent backpressure on the relief valve.
    • Ensure the drain line terminates in an air gap, preventing any possibility of cross-connection.
  5. Controle na installatie:
    • Slowly open the upstream shutoff valve, then the downstream shutoff valve, to gradually fill the system and prevent water hammer.
    • Controleer alle verbindingen op lekkages.
    • Perform initial testing by a certified backflow prevention tester to ensure proper operation and compliance with local codes.

5. Gebruiksaanwijzing

The Watts 009M2 is designed for continuous pressure operation. Normal operation involves the device being fully open, allowing water to flow through the system while providing backflow protection.

6. Onderhoud

Regular maintenance is critical for the reliable performance of your backflow preventer. The modular design and single access cover simplify servicing.

7. Probleemoplossing

ProbleemMogelijke oorzaakOplossing
Water discharge from relief valve (continuous)
  • Fouled first check valve
  • Damaged relief valve seat or disc
  • Excessive backpressure
  • Clean or repair first check valve.
  • Inspect and replace relief valve components.
  • Identify and correct source of backpressure.
Geen waterstroom of verminderde waterstroom
  • Shutoff valves closed
  • Debris obstructing flow
  • Fouled check valves
  • Zorg ervoor dat de afsluitkleppen volledig open staan.
  • Isolate and inspect for debris.
  • Clean or repair check valves.
Lekken van verbindingen
  • Onvoldoende afgedichte schroefdraad
  • Beschadigde pakkingen
  • Re-apply thread sealant and tighten connections.
  • Inspect and replace gaskets.

For issues not listed or if troubleshooting steps do not resolve the problem, contact a certified plumbing professional or Watts technical support.

8. Specificaties

Modelnummer0063010 (009M2)
Backflow Preventer TypeMontage van de zone met verlaagde druk
LichaamsmateriaalBronzen
Aansluitmaat inlaat/uitlaat2 Inches (50 MM)
Inlet/Outlet Connection TypeFemale Threaded NPT
Maximale werkdruk175 psi (12.10 bar)
Maximale temperatuur180°C (82°F)
Min. temperatuur33°C (0.5°F)
BeschermingstypeBackpressure and Backsiphonage
Productafmetingen (L x B x H)22 x 10 x 8 inch
Artikelgewicht27 pond
Lead Free StatusNO (For non-potable use only)

9. Garantie en ondersteuning

Specific warranty information for Watts products is typically provided with the product packaging or available on the official Watts website. Please refer to these resources for the most current warranty terms and conditions.

For technical support, replacement parts, or further assistance, please contact Watts customer service or visit their official website. Ensure you have your product model number (0063010) and serial number (if applicable) ready when contacting support.

Watts-functionaris Webwebsite: www.watts.com

Gerelateerde documenten - 0063010

Preview Technische specificaties voor de Watts LF909-serie drukverlagende zone-assemblage
Uitgebreide technische specificaties voor de Watts LF909-serie drukreduceerzone (2½" - 10"). Hierin worden de kenmerken, werking, materialen, afmetingen en capaciteit van dit loodvrije terugstroombeveiligingsapparaat met geïntegreerde overstromingssensor beschreven.
Preview Watts Series 009, LF009, LFU009, SS009, U009: Installatie-, onderhouds- en reparatiehandleiding
Deze uitgebreide handleiding van Watts biedt essentiële richtlijnen voor de installatie, het onderhoud en de reparatie van de terugstroombeveiligingen uit de series 009, LF009, LFU009, SS009 en U009. De handleiding beschrijft veiligheidswaarschuwingen, installatieprocedures, inspectie, onderhoud, probleemoplossing en garantie-informatie voor deze cruciale terugstroombeveiligingen.
Preview Watts Series 909, LF909, 909RPDA Reduced Pressure Zone Assemblies Installation, Maintenance, and Repair Manual
Comprehensive guide for the installation, maintenance, and repair of Watts Series 909, LF909, and 909RPDA Reduced Pressure Zone Assemblies, including safety warnings, installation guidelines, testing procedures, servicing instructions, troubleshooting, and warranty information.
Preview Technische specificaties van de Watts LF909 drukreduceerzone-assemblages uit de Watts-serie.
Gedetailleerde technische specificaties voor de Watts Series LF909 drukreduceerzone-assemblages, inclusief kenmerken, werking, afmetingen, gewicht en capaciteit. Ontworpen voor het voorkomen van kruisbesmetting met drinkwater.
Preview Watts Series 009, LF009, LFU009, SS009, U009 Reduced Pressure Zone Assemblies Installation, Maintenance, and Repair Manual
Comprehensive guide for the installation, maintenance, and repair of Watts Series 009, LF009, LFU009, SS009, and U009 Reduced Pressure Zone Assemblies, covering safety, installation procedures, annual inspection, troubleshooting, and service. Includes details on flood sensor activation and connection kits.
Preview Watts Series LF919 drukreduceerzone-unit: installatie-, onderhouds- en reparatiehandleiding
Uitgebreide handleiding voor het installeren, onderhouden en repareren van de Watts Series LF919 drukreduceerzone (1/2" - 2"). Bevat veiligheidswaarschuwingen, installatieprocedures, onderhoudsinstructies en tips voor het oplossen van problemen.