Algemeen

  • The IPGSM-4G is a commercial fire alarm communicator that offers contact ID reporting with any Fire Alarm Control Panel (FACP) that has a built-in dialer.  This single or dual path communicator connects directly to the primary and secondary communication ports of a fire panel’s Digital Alarm Communicator  Transmitter (DACT). It offers three selectable reporting paths which include: Cellular only, IP only, or IP primary/cellular backup. All signals from the IPGSM 4G are delivered to Honeywell’s AlarmNet® Network Control Center, which routes highly encrypted Ethernet data packets via a customer provided internet connection or cellular network to the appropriate central station. The state of the art AlarmNet network control center is fully redundant and monitored 24/7.  AlarmNet has the ability to route messages using AlarmNet-I and 800 PLUS services, providing true redundancy and multi-path message delivery.
  • Alternatieve communicatiemethoden zijn van cruciaal belang op de markt vanwege VoIP (Voice over IP), migratie van POTS (Plain Old Telephone Service) en de groei van digitale radionetwerken. Dankzij de single-path communicatieoplossing van de IPGSM-4G kan één technologie worden gebruikt (IP of mobiel) om de juiste connectiviteit met een centraal station te bieden. Voor extra betrouwbaarheid maakt onze exclusieve dual path-oplossing het mogelijk om beide technologieën (IP en mobiel) samen te gebruiken voor maximale overlevingskansen of voor lokale jurisdictievereisten die een duaal technologiesysteem specificeren.

KENMERKEN & VOORDELEN

  • Saves the cost of two dedicated phone lines.
  • Single or dual path communications- (can communicate to central station using cellular technology, internet, or both.
  • Requires no change to the existing Fire Alarm Control Panel configuration. (Connects directly to the primary and secondary telephone ports of a DACT.)
  • Operates over the following communication protocols: HSPA+ (4G) HSPA (HSDPA & HSUPA) (3G), EDGE (2G GPRS) (2G).
  • Selectable reporting paths and supervision intervals to meet NFPA 72, chapter 26 requirements. (Compliant with NFPA 72 2010 and 2013 supervision requirements.)
  • Works over any type of customer provided Ethernet 10/100 based network connection (LAN or WAN), DSL modem or cable modem.
  • Data transmits over standard contact-ID protocol but is secured with the industry’s advanced encryption standard (AES 256 bit).
  • Supports both dynamic (DHCP) or Public and Private Static IP  addressing.
  • Built-In Power Supply module: On board charging circuit design accommodates back-up battery. Includes primary power and battery supervision.
  • Diagnostic LEDs : Signal strength and status indicators.
  • Reliable connection: IP and GSM connection tested every day.
  • QOS: Quality of Service diagnostics via AlarmNet conveys vital communicator information including when message was received, signal strength, and message path used.
  • 7720P Hand-held programmer for easy setup.

De IPGSM-4G is ontworpen om te werken via de meest gangbare mobiele netwerken, waaronder 3G en HSPA+. De multi-GSM-platformtechnologie kiest automatisch het best beschikbare mobiele signaal in het gebied op basis van de signaalsterkte en past zich naadloos aan om kritieke levensveiligheidscommunicatie te behouden. Bovendien kan het worden aangesloten op elk type door de klant geleverde Ethernet 10/100 basisnetwerkverbinding (LAN of WAN), DSL-model of kabelmodem. Dankzij onze selecteerbare rapportagepadfunctie kan de radio worden geconfigureerd voor een oplossing met één of twee paden, evenals de juiste supervisie-intervallen op basis van NFPA 72-vereisten. (Zie onderstaand diagram voor selecteerbare paden en intervallen voor bewakingstijdstippen.)Honeywell-IPGSM-4G-Single-or-Dual-Path-Commercial-Fire-Communicator-fig-1

Werking

Wanneer er een gebeurtenis plaatsvindt, gaat de brandmeldcentrale van de haak om de meldkamer te bellen. De IPGSM-4G kiezerregistratiemodule detecteert de toestand van de hoorn van de haak en geeft de brandmeldcentrale een kiestoon. Wanneer het brandmeldpaneel de kiestoon detecteert, begint het de meldkamer te bellen. Nadat het kiezen is voltooid, stuurt de kiezerregistratiemodule een handdruk terug naar de brandmeldcentrale. De brandmeldcentrale stuurt vervolgens de contact-ID-rapporten naar de Dialer Capture Module, die op zijn beurt een kiss-off verzendt nadat de melding met succes is ontvangen van de brandmeldcentrale. De Dialer Capture Module stuurt de contact-ID-rapporten naar de IPGSM-communicatiemodule. Wanneer alle rapporten zijn verzonden, gaat de brandmeldcentrale op de haak. De IPGSM-communicatiemodule verzendt vervolgens de berichten naar de meldkamer via het GSM-netwerk of internet (afhankelijk van de configuratie).

Makkelijk te programmeren

The IPGSM-4G communicator can be pre-programmed using the 7720P programmer to enter all central-station information. This is saved to the IPGSM-4G communicator panel memory. When the IPGSM-4G communicator is installed at the site and connected to the Internet/Intranet, it registers itself with the AlarmNet receiver.
Voor de meeste installaties zijn de enige vereiste parameters:

  • Primary City ID (two digits) obtained from your monitoring station.
  • Primary Central Station ID (two digits) obtained from your monitoring station.
  • Primary Subscriber ID (four digits) obtained from your monitoring station.
  • Communication Module’s MAC ID, and MAC CRC number located on outside of box, and inside of the module.

Al deze parameters worden toegewezen door de meldkamer.
Opmerking: Some assembly is required. See Installation and Setup Guide
#800-12454 for full details.

Fire Communicator Vermogen
De IPGSM-4G is compatibel met brandmeldcentrales die het communicatieformaat Contact ID gebruiken, zoals beschreven in de SIA DC-05-standaard.

AlarmNet
Honeywell's AlarmNet is de landelijke leider op het gebied van alarmcommunicatietechnologie sinds 1986. Ons radionetwerk is een betrouwbaar alternatief voor de verzending van alarmsignalen en biedt uitgebreide dekking in de Verenigde Staten en Canada. AlarmNet Netwerk Controlecentrum verwerkt signalen van krachtige servers op meerdere locaties uitgerust met 24/7 infrastructuurondersteuning. Het AlarmNet-netwerk bestaat uit redundante hardwareservers, hot back-up databases en generatoren met batterijback-up op alle locaties om de continuïteit van de dienstverlening te waarborgen. Signalen van Alarm-Net worden verzonden naar de ontvangers van het centrale station met behulp van meerdere communicatiepaden, bestaande uit internet, radionetwerk of gratis POTS-service.

Installatievereisten

UL NALEVING
To meet UL864/NFPA, ensure the following:

  • IPGSM-4G must be installed in accordance with NFPA (National Fire Protection Association) standards 70 and 72.
  • IPGSM-4G must be mounted in the same room and within 20 feet of the fire panel.
  • IPGSM-4G, and all equipment used for the IP connection (such as the router, hub, modem, etc.) shall be listed, must be powered from an un-switched branch circuit, and be provided with appropriate standby power.
  • IPGSM-4G must use the 7AH battery (not supplied) to provide 24-hour backup capability.

IPGSM-4G Technische specificaties

ELEKTRISCHE
Transformator:

  • primair: 120VAC, 60Hz, 0.5A
  • Tweede: 18VDC, 50VA

Accu:

  • One 12 V 7.0 AH lead-acid battery: (niet geleverd)
  • Batterij laadstroom: 1 Amp maximaal
  • Battery discharge current: Standby 230mA, Active 950mA

KAST SPECIFICATIES

  • Afmetingen: 14.875″ H x 12.75″ W x 3.0″ D (37.8 cm H x 32.4 cm W x 7.6 cm D)
  • Kleur: Rood

VERZENDING SPECIFICATIES

  • Gewicht: 5.3 lbs. (6.94 kg)
  • Afmetingen: 15.625″ H x 13.79″ W x 9.25″ D (39.7 cm H x 34.9 cm W x 23.9 cm D)

TEMPERATUUR- EN VOCHTIGHEIDSBEREIK
This system meets NFPA requirements for operation at 0 -49°C/32 – 120°F and at a relative humidity 93% ± 2% RH (non condensing at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system’s standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 – 27°C/60 – 80°F.

PRODUCTLIJN INFORMATIE

IPGSM-4G: Internet and Digital Cellular Fire Alarm Communicator Panel. Includes red cabinet with Ademco® key and lock, wall outlet box, Dialer Capture Module, IGSM Communications Module, antenna & mounting adapter, PowerBoost1 power supply, LED display board, transformer, manual, & required screws, cables, etc.
Antenna External Hardware

  • GSM-ANT3DB: 3db gain external/remote antenna
  • WA7626-CA: SNA to N Adapter
  • 7626-50HC: 50 ft. antenna cable, low loss
  • 7626-25HC: 25 ft. antenna cable, low loss

Opmerking: The GSM-ANT3DB and the WA7626-CA are both required for installing an external antenna along with the necessary cable needed (7626-50HC: 50 ft. or 7626-25HC: 25 ft.)
andere accessoires

  • 7720P: IPGSM-4G hand held programmer.
  • HPTCOVER: Plug-in transformer box for IPGSM communicator.
  • BAT-1270: Battery 12 Volts, 7 AH, sealed.

AGENTSCHAPPEN EN GOEDKEURINGEN
The listings and approvals below apply to the basic IPGSM-4G communicator panel. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process.
Raadpleeg de fabriek voor de laatste lijststatus.

  • UL Listed: S789
  • CSFM: 7300-1645: 0199
  • FDNY: COA #6219

Ademco® en AlarmNet® zijn geregistreerde handelsmerken van Honeywell International Inc.
Dit document is niet bedoeld om te worden gebruikt voor installatiedoeleinden. We proberen onze productinformatie up-to-date en nauwkeurig te houden. We kunnen niet alle specifieke toepassingen dekken of op alle vereisten anticiperen. Alle specificaties kunnen zonder voorafgaande kennisgeving worden gewijzigd.

Voor meer informatie
Learn more about Honeywell’s IPGSM-4G and other products available by visiting www.honeywellpower.com.
Honeywell Power-producten
Clintonville Road 12
Northford, CT 06472-1610
877.HPP.POWR
www.honeywell.com
brandalarmresources.com

Documenten / bronnen

Honeywell IPGSM-4G commerciële brandmelder met enkel of dubbel pad [pdf] Gebruikershandleiding
IPGSM-4G Commerciële brandcommunicator met enkel of dubbel pad, IPGSM-4G, Commerciële brandcommunicator met enkel of dubbel pad, Commerciële brandcommunicator met enkel pad, Commerciële brandcommunicator met twee paden, Commerciële brandcommunicator, Brandcommunicator

Referenties

laat een reactie achter

Uw e-mailadres wordt niet gepubliceerd. Verplichte velden zijn gemarkeerd *